Total GSF: 177,019 square feet
Office/Storage: 7,362 square feet
Data Halls: 89,097 square feet
Power
- Utility Capacity – Approximately 150-175MW, with 30MW available for S7 plus a little bit of load over in S5. Utility growth is dependent on customer load growth.
- Utility Voltage – 34.5kV
- Number of Utility Feeders – Two currently with the third on the way, end game is five including the service to permanently feed S7.
- Number of Transformers on site – 15 plus 1 house for Sterling Vll; no substation transformers for this site
- UPS Configuration and capacity – 6MW block redundant, 5-make-4 blocks
- Generator Power – 33.75MW plus 1.75MW house
Cooling
- Chiller Plant – Each hall is nominally 6 MW at N+1.
- Data Hall – 225-ton CRAH units, N+2 configuration
Security
- Physical – Anti-scale fence around the property; electronic gates, and gate arms at the entrance to the site
- Guards – Secure entry into space via Security Office with guards
- Electronic – Electronic surveillance, card reader access control to building and space
- Perimeter fence
, other data centers in Sterling or operated by CyrusOne Data Centers, please try our