Private Cabinets
Partial Cabinets
Bare Metal Servers
On-Net Products
- IP Transit
- Ethernet Transport Services
Standard Rack Configuration
- 42U APC Cabinets (Model AR3100)
- Power extra (110v/20amp or 2X 110v/20amp is standard)
Carrier Availability
- Verizon
- Cox Communications
- Windstream
- Zayo
Facilities
- 12,900 square feet of raised floor colocation space
- Manned 24x7 840 square foot NOC
Security
- C*CURE Card-Reader Access Control System
- (14) card readers located at essential access points entrance into data centers require HID card swipe and unique pin code for access
- (18) cameras tied into software with recording and 24/7 monitoring capabilities
HVAC
- 28 CRAC units, 10 ATS, and 18 Airflow with rooftop mounted condensers
- Separate remote mounted humidifiers for HCs.
- 1 Carrier rooftop unit for Battery room
UPS Systems
- 3 UPS Modules @ 375 KVA each (MGE EPS 6000) working in parallel
- 1 MGE Static Transfer Switch
Battery Room
- 3 Strings (total number of batteries: 240)
- C&D Dynasty Model UPS12-400MR Sealed
Electrical/Fire/Monitoring
- United Power PDUs (8) and EDMs (8)
- 480v 3-phase utility feed - 3,000 amps
- Fire Detection and Suppression consists of above and below floor smoke heads, FM200 - tanks, and a pre-action sprinkler system in hosting centers.
Generator Systems
- Spectrum Diesel Generator, 1500kw/1875kVA
- 5,000 gallon diesel storage tank
- Auto Transfer Switch
- "Tap Box" connection in place for portable generator emergency usage
Pricing & Services
If you are looking for colocation, cloud, connectivity or other services in
Cogent Herndon, other data centers in Herndon or operated by Cogent Communications, Inc., please try our
free quote service or reach out for a
free consultation about your data center needs.