Campus / Facility
• Data Center facility is located 16 feet underground to provide the best protection possible from adverse weather events (such as tornadoes)
• Exterior walls are 13” thick reinforced concrete with extensive water control systems on the exterior to prevent water intrusion from above
• Floor slab has waterproof barrier and additional subfloor slab to protect against water intrusion from below
• Facility consists of two Data Center pods, each capable of housing up to (75) 42U racks
• Over 30,000 sq ft of available D.R. office space, built to customer specs
• Campus has an on-site cafe, walking trails in a park-like setting, mens/womens locker rooms w/showers, ample free parking, 24x7 security with roving indoor and outdoor patrols, and a top-rated hotel in close proximity to the facility
Security
• SAS 70 Type II and PCI-DSS certified facilities
• Biometric access control system at all facility entrances
• All access to the facility is via TulsaConnect escort only
• Campus has 24 x 7 security on-site
Environmental
• Liebert 20-ton DX CRAC units provide precision cooling and are arranged in a N+1 configuration
• Racks are arranged in a standard hot-aisle / cold-aisle configuration with Simplex airflow containment system
• Environmental monitoring, including temperature, humidity, moisture, and sound sensors
Electrical Power
• Campus has true dual-substation electrical feeds with automatic switchgear to switch between substations
• Eaton 9395 UPS system with redundant power modules (N+1) and wrap-around maintenance bypass
• On-site 800KW CAT diesel generators (1 per pod) will support the facility load in the event of a utility power failure
• ASCO 7000-series ATS w/bypass isolation feature allowing concurrent maintenance
• ASCO 7000-series MTS allowing selection of on-site or portable generator
• Generator tap on building exterior for portable generator hook-up in case of primary generator failure
• Should any of the on-site generators fail, TulsaConnect owns a portable, trailer-mount generator that can be brought on-site within 1 hour
Fire Suppression
• ECARO clean-agent gas fire suppression system throughout the entire Data Center space
Network
• Redundant Gig-E Internet backbone connections from Level(3), Time Warner Telecom, Cox, and Cogent
• Juniper M-series routers at used at the network edge, and Cisco carrier-class routing switches at the core and distribution layer (IPv6 ready)
• Multiple paths between distribution layer and core network, with OSPF and iBGP protocols for dynamic routing
• Wide selection of fiber providers, including EasyTEL, TW Telecom, AT&T, Verizon Business, and Cox. In addition, access to PAETEC, MBO, and Level(3) fiber is available at our DC2 facility
• Ability to provide both MPLS and Metro Ethernet connections directly to customer equipment
• Gigabit interconnects over fiber between DC1 and DC2 for intra-DC traffic
about your data center needs.
.