Enabled by a wealth of high-speed connectivity options, power rates 20% below the national average, more than 33% of power generation coming from renewable sources, and tax incentives that flow directly to the Data Center tenants, the city of Omaha and state of Nebraska have signaled they are serious players in the market.
Location
1. Accessible & Available
-Close proximity to Omaha airport
-Focal point for long-haul & trans-continental fiber
-Easy access to I-80
-Located in Omaha DC Business Park
-Planned power developed area
2. Risk-Free Environment
-Low seismic risk
-Low tornado probability
-Not in airport landing path
-Outside 500-year floodplain
-Low traffic area
3. Low Cost, Big Reward
-Annual average electricity cost is 20% below national average
Building & Expansion
1. Proven Design
-Hardened 10" pre-cast concrete structure
-Multi-zoned, dual interlocked, dry pipe sprinkler
-36 in. raised floors
-VESDA
2. What's to Come
-Built in 2010
-Retrofitted in 2017
-Total sq. ft. 16,377
-5,000 sq. ft. raised floor
-Plans for 25,000 sq. ft. raised floors
-Individual rack & cage space available
-Custom suite offerings
-Scalable power & cooling that can be dedicated, semi-dedicated or shared
-10 in. reinforced precast walls
-Tier 3 rated facility with a 120 mph wind rating
-Build-up/burn-in room
Uninterrupted Power
-2 separate utility feeds (2 - 1,500 KVA transformers)
-Redundant substations
-Generator Power (2N) 2 - 1.5 MW Cat Generators with 36-hr. runtime fully loaded (3,300-gallon fuel tanks)
-2 complete separate electrical rooms
-Each electrical room is outfitted with (1) 750 KVA NXL Liebert UPS (plumbed for 2 for a max 1.5MW)
-2 battery rooms
Connectivity
-Four Carriers have POPs with diverse routes
-Variety of LE dark fiber & lit services
-Private connectivity to KC and Altoona DCs
-Private connectivity to local carrier hotel
Security
1. Physical
-Secure check-in process, and key card & biometric scanners
-Video surveillance at perimeter and inside with 91+ days archived video
-Key card activated via hand scan and deactivated upon departure
-Two-factor authentication through mantraps, utilizing key card access, pin code, hand geometry biometrics, and tailgate sensors
-Entry into white floor space requires additional hand scan and key card access for multiple levels of secure checkpoints
-High definition video surveillance cameras located in each aisle
-All DC cabinets are equipped with combo locks and each cage or private suite is secured with either key card or biometric controls
2. Compliance & Operations
-PCI-DSS v2.2 & HIPAA compliant
-SSAE 16 SOC 1, 2, and 3 Type II audited
-ISO 20000 & ISO 27001 certified
-24x7x365 manned Operations Center
3. Building Management System
-Powered by Tridium Niagara AX
-Centralized management of critical infrastructure equipment
-Historical data available for trending
Cooling
-Motivair Chillers (418kW) each. Max design 1.5mW cooling
-Liebert CRAH units (N+1) configuration
-N+1 built-in redundancy
-36 in raised floors throughout
-Dual power fed HVAC units with Variable Speed Fans
-Humidity set point of 44