MECHANICAL SYSTEM
--------------------------
a- Cooling System: Refrigerant cooling system.
b- CRAH redundancy: N+1, Data Center equipment demand cooling load is 1000 W/m2
c- Fuel Oil: Generator fuel oil storage 48 hours capacity
d -BMS : Computerized Building Management System M&E equipment verification and management
ELECTRICAL SYSTEM
-------------------------
a- Design Load: The electrical connected load is 1.2 MVA with a demand load of 0.9 MVA.
b- Transformer: 2 x 1500 kVA Power Transformer, 380/220V, 3P, 4W, 60Hz.
c- Generators: 3 x 2354 kVA/1883 kW Continuous Rated Generator configured in N+1
d- Paralleling Switch gear: One set of paralleling switch gear for concurrently maintainable requirements which is controlled and monitored by Load Shedding Panel
e- UPS: parallel redundant system in N+1 configuration, 200KVA modular units with 30 minute battery autonomy at full load. 1000 W/m2 for Data Center
f- Rectifier System: Active + Active System, (N+N) at 200 W/m2, 1000 Ah for 2 hrs + 2hrs battery autonomy time
g- Security System : IP access control System and Analog CCTV system