d-Site Scan: Computerized Building Management System M&E equipment verification and management
ELECTRICAL SYSTEM ------------------------- a-Design Load: The electrical connected load is 1.2 MVA with a demand load of 0.9 MVA.
b-Transformer: 2 x 1500 kVA Power Transformer, 380/220V, 3P, 4W, 60Hz.
c-Generator: 3 x 2354 kVA/1883 kW Continuous Rated Generator configured in N+1.
d-Paralleling Switch gear: One set of paralleling switch gear for concurrently maintainable requirements which is controlled and monitored by Load Shedding Panel.
c-UPS: Parallel redundant system in N+1 configuration, 200KVA modular units with 30 minute battery autonomy at full load. 1000 W/m2 for Data Center.
d-Rectifier System: Active + Active System, (N+N) at 200 W/m2, 1000 Ah for 2 hrs + 2hrs battery autonomy time.
e-Security System: IP access control system and Analog CCTV system