Data Center Map

Fiber 23

Total installed power 100 KW. The power supply consists of two independent transformers of 200 KW each placed at a distance of 70 m from each other. 2 Legrand modular UPSs of 100 KW each. Ensure electrical continuity for the server room. 1 Legrand 80 KW modular UPS. It guarantees the electrical cont
Company ProfileVisit Website
Fiber 23

IP Transit


Total installed power 100 KW. The power supply consists of two independent transformers of 200 KW each placed at a distance of 70 m from each other. 2 Legrand modular UPSs of 100 KW each. Ensure electrical continuity for the server room. 1 Legrand 80 KW modular UPS. It guarantees the electrical continuity of air conditioning systems. At least 30 minutes of autonomy provided by the UPS batteries until the generators are turned on. 250 KW of power provided by 2 electric generators. They start up in 10 seconds from the moment the electricity supply is interrupted. Each rack is powered by two separate BUS Bar circuits. Each circuit is powered by a UPS.

Fiber 23 is registered with presence in 1 data centers.
See the data centers with network presence on the map below.