COMPUTER ROOM SPECIFICATIONS
Available rooms 7 dedicated data floors plus 1 half floor on ground level each with standard critical power of 1.5MW or 2.0MW per data floor, and high density ready.

Typical data floors provide 10,000 SF for IT equipment, ~20,000 GSF, and cabinet space 600 standard 24’W x 48”D or 370 standard 32”W x 48”D per data floor. Standard power density of 150 watts per square foot with optional density of 200 watts per square foot

Structural slab to slab floor heights are 16’6” with loading of over 200 pounds per square foot.

19,140 SF of office available for lease and ~5,000 SF storage available in basement level

7x24x365 Security with check points for all access, ballistic glass and walls, electronic access with dual authentication and minimum 1 biometric reader. Video surveillance 7x24x365 of all exterior and interior areas, and minimum 30 days of archive.

CRITICAL POWER
Total megawatts 30 MW

UPS SYSTEMS
Description - High efficiency static UPS
Redundancy - N+1 or 2N as required

GENERATORS
Description - 2.75 MW diesel generator
Redundancy - N+1 or 2N as required

ON SITE FUEL CAPACITY
5 x 50,000 L + 1 x 30,000 L underground diesel storage
24 hours minimum run time

HEAT REJECTION SYSTEMS
Distributed and N+1 redundant KyotoCooling systems dedicated per data floor.
Annualized PUE of 1.2 or better unaffected by critical load utilization.

PDUs
250 amp overhead busway, optional multiple 400 KVA PDUs, 480V primary, 400/230V
secondary available. 2N redundancy.

COMMUNICATIONS
2 separate network points of entry with diverse underground duct banks to local network
Dedicated diverse conduits and risers to each data floor.
Carrier neutral facility with multiple carriers.

FIRE PROTECTION
Double interlocked pre-action dry type sprinkler system with VESDA throughout building

DESIGN PUE
Montreal NGDC is designed to be best in class with an annualized PUE of 1.20 or better regardless of critical load utilization




Urbacon DC Montreal - 544 Inspecteur
Pricing & Services
If you are looking for colocation, cloud, connectivity or other services in Urbacon DC Montreal, other data centers in Montreal or operated by Urbacon Data Centre Solutions, please try our free quote service or reach out for a free consultation about your data center needs.
Advertisement
Nearest Data Centers
The below data centers are located closest to 544 Rue de L'Inspecteur.
DistanceData CenterAddress
55.1 milesQScale Q01 Campus2280 Albert-Dion St
61.97 milesOricom Internet Colocation350 Charest
62.94 milesOricom400 Nolin
65.61 milesVantage QC2 - Quebec City2675 Boulevard du Parc Technologique
102.51 milesNordik DC4155 rue burrill
110.69 milesNautilus East Millinocket51 Main St
124.95 milesSNS Littleton, NH775 Industrial Park Rd.
125.82 milesAmazon AWS YUL - 1790 Lionel-Boulet A1790 Boulevard Lionel-Boulet
125.84 milesAmazon AWS YUL - Lionel-Boulet Campus1790 Boulevard Lionel-Boulet
125.87 milesAmazon AWS YUL - 1790 Lionel-Boulet B1790 Boulevard Lionel-Boulet
Urbacon Data Centre Solutions

Urbacon Data Centre Solutions

Data Center Operator at
Urbacon DC Montreal
544 Rue de L'Inspecteur
Headquartered in Toronto, ON

8